SHORT COMMUNICATION
Year : 2016  |  Volume : 18  |  Issue : 2  |  Page : 135-137

Water usage in a multi-speciality hospital and its effective management


1 Department of Economics, Newcastle University Business School, UK
2 Faculty of Economics and Business, University of Groningen, Groningen, The Netherlands
3 Department of Microbiology, Tata Medical Center, Kolkata, West Bengal, India
4 Department of Maintenance Engineering, Tata Medical Center, Kolkata, West Bengal, India
5 Department of Medical Administration, Tata Medical Center, Kolkata, West Bengal, India

Date of Web Publication30-Nov-2016

Correspondence Address:
Dr. Sanjay Bhattacharya
Department of Microbiology, Tata Medical Center, Kolkata, West Bengal
India
Login to access the Email id

Source of Support: None, Conflict of Interest: None


DOI: 10.4103/0972-1282.194956

Rights and Permissions
  Abstract 

Context: Water is an important resource for hospitals. There are few studies about the quality, quantity and cost of water that is required for health care. Aims: To study the quality, quantity, cost and applications of water in a hospital. Settings and Design: Observational study. The study was done in a cancer hospital in eastern India. Methods and Material: Water generation and consumption patterns and costing were assessed after: Discussion with the engineers; analysis of documented records; observation of patient/visitor/staff behaviours; measurement of flow rates and metered readings; Individual water consumption surveys. Statistical Analysis Used: None. Results: The total filtered reverse osmosis (RO) water used by the hospital per day was 200,000 L. This equated to 1093 L/patient/day. The volume of filtered reversed osmosis water consumed showed that the total water usage for drinking was 1%, water usage for hand-washing was 18%, water usage for showering was 6%, kitchen water consumption was 2%, housekeeping activities usage was 4%, central sterile supply department usage was 4%, heating, ventilation, and air conditioning systems usage was 36%, hot water consumption was 5% and toilet flush usage was 24%. Cost was Rs. 1119/- for 10,000 liters of RO water and about Rs. 31/- for 10,000 liters of raw water. Conclusions: The economics of hospital water both in terms of consumption and cost is a valuable source of information for hospital planners, administrators and hospital engineers.

Keywords: Conservation, health economics, hospital water, quality monitoring, reverse osmosis
Key Messages:

  1. Water is a precious resource. Wastage needs to be minimized
  2. It is important for hospitals to monitor its water usage
  3. Safe and adequate water is essential for effective hospital infection control and monitoring its microbiological quality is of paramount importance


How to cite this article:
Collett S, Samarin I, Bhalchandra R, Soundaranayagam JR, Garai S, Chandy M, Bhattacharya S. Water usage in a multi-speciality hospital and its effective management. J Acad Clin Microbiol 2016;18:135-7

How to cite this URL:
Collett S, Samarin I, Bhalchandra R, Soundaranayagam JR, Garai S, Chandy M, Bhattacharya S. Water usage in a multi-speciality hospital and its effective management. J Acad Clin Microbiol [serial online] 2016 [cited 2023 Dec 2];18:135-7. Available from: https://www.jacmjournal.org/text.asp?2016/18/2/135/194956


  Introduction Top


Water is a vital resource for health-care activities. Data from 54 low resource low- and middle-income countries in the six World Health Organization regions (located in Africa, Americas, South-East Asia, Europe, Eastern Mediterranean and Western Pacific) showed 38% of health-care facilities did not have an improved water source(s), 19% did not have improved sanitation and 35% did not have water and soap for hand-washing. [1] Improved water source uses uniform definitions for safe water sources promoted by The United Nations Children's Emergency Fund. These include the following: Piped, public tap, standpipe, tubewell/borehole, protected dug well, protected spring, rainwater. The improved water source should ideally be within 500 m of the facility. [1]


  Materials and Methods Top


Study design

The current study was conducted in an 183-bed cancer hospital in Eastern India, with the following objectives:

  1. Water audit regarding consumption for various activities and quality
  2. Estimation of the cost of hospital water
  3. Developing water management recommendations.


Water generation and consumption patterns and their costing were assessed after:

  • Discussion with the engineers
  • Analysis of documented records
  • Observation of patient/visitor/staff behaviours
  • Measurement of flow rates
  • Metered readings
  • Individual water consumption surveys.


The total dissolved solids (TDSs) of the hospital reverse osmosis (RO) water is measured by a digital conductivity meter, the free chlorine by a digital chlorine meter and microbiology by the membrane filtration technique (Millipore) and quantitative culture on MacConkey agar (HiMedia). [2],[3]


  Results Top


There are two main sources for our hospital water - two deep borewells to source the groundwater - and government water supply.

The raw water analysis of our hospital showed that the total hardness (as calcium carbonate) of the raw water to be 362 mg/L (desirable <300 mg/L), iron to be 2.54 mg/L (desirable <0.3 mg/L), TDS to be 835.7 mg/L (desirable <500 mg/L) and total coliforms to be 23 most probable number (MPN)/100 mL and faecal coliforms (3.6 MPN/100 mL).

However, the TDS of the hospital RO water is maintained at <100 ppm, the free chlorine between 0.2 and 0.5 ppm and microbiology adhered to the following standards: Zero coliforms and Pseudomonas per 250 mL of water, total aerobic colony count of <2000 CFU/mL of water. [2],[3]

The total filtered water used by the hospital per day was 200,000 L. This equated to about 1093 L/patient/day (200,000 L/day divided by 183 patients). The total water used for drinking was 2048 L/day (1%), for hand-washing (including surgical hand scrubbing) 36,987 L/day (18%), for showering 11,948 L/day (6%), kitchen water consumption 4525 L/day (2%), housekeeping activities used 7361 L/day (4%), central sterile supply department (CSSD) 7246 L/day (4%), heating, ventilation, and air conditioning (HVAC) systems 72,000 L/day (36%), hot water consumption 10,000 L/day (5%) and toilet flush usage 47,885 L/day (24%) [Figure 1]. This calculation amounted to a total monthly water cost of Rs. 682,911 ($10,506) [Table 1]. The cost of water was highly sensitive to the cost of electricity with an estimated 66.6% increase in water cost if the cost of electricity in India was raised to the equivalent of that in Brazil and an estimated 22.2% rise in cost if the cost of electricity was equated to that in Russia. The rainwater harvesting potential for the hospital was calculated to be 4,409,120 L for the period from July to October (the rainy season for the region).
Figure 1: Water used in Tata Medical Center, Kolkata, West Bengal, India

Click here to view
Table 1: Monthly cost of hospital water in Tata Medical Center, Kolkata, India


Click here to view



  Discussion Top


According to the 'Emergency water supply planning guide for hospitals and health care facilities' of the Centers for Disease Control and Prevention and American Water Works Association 'health care facilities need to develop an Emergency Water Supply Plan to prepare for interruption of normal water supply. [4] Water supply interruption in health-care settings could result in serious compromise of hand-washing and hygiene, drinking, food preparation and hygiene, flushing toilets and bathing patients, laundry and other services provided by central services (e.g., cleaning and sterilisation of surgical instruments), reprocessing of medical equipment (e.g., endoscopes, surgical instruments and accessories), patient care (e.g., haemodialysis, hemofiltration, extracorporeal membrane oxygenation, hydrotherapy), fire suppression sprinkler systems, water-cooled medical gas and suction compressors (a safety issue for patients on ventilation), HVAC and decontamination. [4] Every health care establishment must have a "Water Use Audit plan" which should include (a) water usage under normal operating conditions, (b) identification of essential functions and minimum water needs, (c) identification of emergency water conservation measures and (d) identification of emergency water supply options, (e) development of emergency water restriction plan. [4]

Raw water analysis of our hospital showed high total hardness, high iron content, very high TDS and a significant number of total coliforms and faecal coliforms. These properties of high hardness, high iron load, high TDS and the presence of coliforms including faecal coliforms made the raw water unsuitable for applications such as drinking, cooking, hand-washing, bathing, housekeeping, air conditioning, instrument cleaning in CSSD, hot water generation. For all these applications, RO water is used in our hospital. The raw water is used only for specific applications, such as gardening and fire safety purposes.

The infection prevention and control activities (washing, housekeeping) and engineering controls dependent on water (air conditioning system) would be severely crippled in the absence of good quality water. In one US study, the water consumption per patient bed was 548,128 L/year and expenditure per thousand gallons was $4.64 (for 3785 L). [5] According to the Bureau of Indian Standards for hospitals exceeding 100 beds, the average consumption of water is 450 L/head/day (equating to 164,250 L of water/head/year). [6] In the case of our hospital, the total water consumption per bed was 405,555 L/bed/year (200,000 L/day for 183 beds). This is significantly more than the estimated water consumption for Indian hospitals. This excess water consumption could be due to central air conditioning of our hospital. According to one report published by the California Urban Water Conservation Council HVAC (heating ventilation air-conditioning)consumes maximum water (48%) in a typical commercial building. [7] According to another report, water cost saving opportunities in building HVAC systems include (a) identification and correction of system leaks, (b) using air handler condensate for cooling tower makeup and (c) ensuring closed system water usage. [8] In a Massachusetts study, the percentage of unaccounted water was found to be 9%, HVAC used was 23% of the water and sanitary use was 42%. [9] We intend to use the current analysis for future water management strategies. This may lead to less consumption of water, less waste and ultimately less cost.

Financial support and sponsorship

Nil.

Conflicts of interest

There are no conflicts of interest.

 
  References Top

1.
WHO/UNICEF Report: Water, Sanitation and Hygiene in Health Care Facilities: Status in Low-and Middle-income Countries and Way Forward; 2015. Available from: http://www.who.int/water_sanitation_health/publications/wash-health-care-facilities/en/. [Last accessed on 2016 Apr 25].  Back to cited text no. 1
    
2.
Bhalchandra R, Chandy M, Ramanan VR, Mahajan A, Soundaranayagam JR, Garai S, et al. Role of water quality assessments in hospital infection control: Experience from a new oncology center in eastern India. Indian J Pathol Microbiol 2014;57:435-8.  Back to cited text no. 2
[PUBMED]  Medknow Journal  
3.
Health Protection Agency. The microbiological examination of water samples. National Standard Method QSOP 57 Issue 2; 2005. Available from: http://www.hpa-standardmethods.org.uk/pdf_sops.asp. [Last accessed on 2016 Jul 20].  Back to cited text no. 3
    
4.
Centers for Disease Control and Prevention and American Water Works Association. Emergency Water Supply Planning Guide for Hospitals and Health Care Facilities. Atlanta: U.S. Department of Health and Human Services; 2012. Available from: http://www.cdc.gov/healthywater/pdf/emergency/emergency-water-supply-planning-guide.pdf. [Last accessed on 2016 Apr 25].  Back to cited text no. 4
    
5.
Water Consumption Information for Large Hospitals; 2007. Available from: http://www.eia.gov/consumption/commercial/reports/2007/xls/hospital/H8%20Water%20Consumption_v4.xls. [Last accessed on 2016 Apr 25].  Back to cited text no. 5
    
6.
Bureau of Indian Standards. Code of Basic Requirements for Water Supply, Drainage and Sanitation. Fourth Reprint December, 2010; 1993. Available from: https://www.law.resource.org/pub/in/bis/S03/is.1172.1993.html. [Last accessed on 2016 Apr 25].  Back to cited text no. 6
    
7.
California Urban Water Conservation Council. BMP 9 Handbook: A Guide to Implementing Commercial Industrial and Institutional Conservation Programs. "Annual Report 2001"; 2001.  Back to cited text no. 7
    
8.
Weimar D and Browning A. Reducing Water Costs in Building HVAC Systems; 2010. Available from: http://www.hvacronline.co.za/AFE_Reducing_Water_Costs_in_Bldg_HVAC.pdf. [Last accessed on 2016 Apr 25].  Back to cited text no. 8
    
9.
Water Use Case Study: Norwood Hospital. Massachusetts Water Resources Authority. Available from: http://www.mwra.state.ma.us/04water/html/bullet1.htm. [Last accessed on 2016 Apr 25].  Back to cited text no. 9
    


    Figures

  [Figure 1]
 
 
    Tables

  [Table 1]


This article has been cited by
1 Análise dos usos finais de água em hospital público de Brasília, Brasil
Livia Santana, Daniel Sant’Ana
Engenharia Sanitaria e Ambiental. 2023; 28
[Pubmed] | [DOI]
2 Systematic review of indicators for the assessment of water consumption rates at hospitals
Karmem Julya Miron Batista,Simone Rosa da Silva,Emilia Rahnemay Kohlman Rabbani,Tomi Zlatar
Water Supply. 2019;
[Pubmed] | [DOI]
3 Quantitative Determination of Potable Cold Water Consumption in German Hospitals
Alfonso González,Justo García-Sanz-Calcedo,David Salgado
Sustainability. 2018; 10(4): 932
[Pubmed] | [DOI]
4 Study on the use and consumption of water in Spanish private hospitals as related to healthcare activity
Miguel Gómez-Chaparro,Justo García Sanz-Calcedo,Luis Armenta-Márquez
Urban Water Journal. 2018; : 1
[Pubmed] | [DOI]



 

Top
 
 
  Search
 
Similar in PUBMED
   Search Pubmed for
   Search in Google Scholar for
 Related articles
Access Statistics
Email Alert *
Add to My List *
* Registration required (free)

 
  In this article
Abstract
Introduction
Materials and Me...
Results
Discussion
References
Article Figures
Article Tables

 Article Access Statistics
    Viewed27064    
    Printed575    
    Emailed0    
    PDF Downloaded19    
    Comments [Add]    
    Cited by others 4    

Recommend this journal